Radiant Heat Reducing Glazing Solution

SuperLite I-XL is a patented breakthrough, monolithic technology that reduces the transfer of radiant heat by reflecting heat back towards the fire source. It minimizes the threat of scorching heat which can limit the safe egress of occupants and can cause the fire to spread to adjacent areas. SuperLite I-XL 45/60, the first and only product of its kind to be introduced in the USA, was developed by SAFTI FIRST in 1993 and has been installed in locations throughout the USA Authorities having jurisdiction (AHJs) across the country have approved this non-hose stream tested product because of its ability to reflect radiant heat and stay in the opening for over one hour, allowing for safe egress of occupants. Most AHJs recognize that the hose stream test was designed for structural building integrity and not as a thermal stress test for fire-rated glazing. Sprinkler activation does not compromise the performance of SuperLite I-XL.

For over 20 years, Europe, Japan and other countries have taken advantage of the enhanced safety performance of products like SuperLite I-XL. This radiant heat reducing fire glazing is an excellent choice for schools, hospitals, historical renovations, wilderness/urban interface areas, property line applications, or any areas where safe egress, impact safety and protection from the dangers of radiant heat are a concern. SuperLite I-XL provides greater radiant heat and impact protection than any other monolithic glazing, including ceramics, and is a low cost replacement for unsafe traditional wired glass. It is available in non-directional insulated or directional monolithic makeups. Fire fighters along with code officials have stated their favor of a product like SuperLite I-XL because it is quick and safe to remove in the event of a fire, allowing for access, smoke release and safe egress of occupants.

FEATURES 
  • Optically clear, not tinted or distorted as ceramics are.
  • Blocks up to 90% of dangerous radiant heat compared to wired and ceramic glazing.
  • Tempered to meet the highest federal safety standard, Consumer Product Safety Commission 16CFR 1201 Cat. II, which requires withstanding 400 ft. lbs. of impact.
  • Positive Pressure fire rated to 45/60-minutes without hose stream.
  • Thin directional makeup. Available in non-directional IGU.
  • 1/4” (6mm) for use in standard hollow metal but available up to 1/2” (14mm) where wind or structural requirements are a consideration.
  • Survives thermal shock from sprinklers.
  • USA manufactured for fast delivery.
  • For use in hollow metal, wood, aluminum, or any equally fire-rated framing system.

For information on obtaining AHJ Approval for SuperLite I-XL,
click here.

Fire Rating* Application Max Lite Area** Max W Max H Stops
45 Minutes Doors 3,341 sq. in. 35-1/8” 95-1/8” 5/8"
45 Minutes Sidelites 3,522 sq. in. 35-1/8” 95-1/8” 5/8"
45 Minutes Windows / Transoms 3,522 sq. in. 48” 96” 5/8"
60 Minutes Doors 3,341 sq. in. 35-1/8” 95-1/8” 5/8"
60 Minutes Sidelites 3,341 sq. in. 35-1/8” 95-1/8” 5/8"
60 Minutes Windows / Transoms 3,341 sq. in. 35-1/8” 95-1/8” 5/8"
* SuperLite I-XL is fire tested to UBC 7-2, UBC STD 7-4, NFPA 252, NFPA 257, UL 9, UL 10B, UL 10C, ASTM E2074, ASTM E152, ASTM E2010, and ASTM E163. SuperLite I-XL requires AHJ approval because it carries a conditional listing similar to glass block products.
** Maximum area allowed is 25% of the wall area. Any ratings over 45 minutes should consider the dangers caused by radiant heat.
SPECIFICATIONS 
Thickness: 1/4” (6mm) standard
Weight: 3.0 lbs./sq. ft.
Appearance: Clear, wireless
U-Value: .40
Light Transmission: 73%
STC Rating: 28
LISTINGS 
SuperLite I-XL is patented, listed and labeled with positive pressure by Intertek/Warnock Hersey, Inc. Intertek/Warnock Hersey permanent labels are applied to all glass lites. This product carries a conditional listing. It is a directional product that reduces radiant heat transfer from one side only. Consult special glazing instructions prior to installation. For non-directional make-up, see SuperLite I-XL IGU

  

STANDARDS 

UBC 7-2, UBC STD 7-4, NFPA 252, NFPA 257, UL 9, UL 10B, UL 10C, ASTM E2074, ASTM E152, ASTM E2010, and ASTM E163.

This product requires AHJ approval because it does not pass the
hose stream portion of the fire test.

DELIVERY 
Allow 5 days from confirmed order. Quick ship is available upon request.