Skip to content
  • QUOTE
  • 888.653.3333
  • info@safti.com
  • Products
    • Fire Protective Glass Tested to NFPA 252/257, UL 9/10C, ULC S104/S106; Blocks smoke and flames.
    • SuperLite® I
    • SuperClear® 45-HS
    • SuperClear® 45-HS-LI
    • SuperLite® I-XL
    • SuperLite® I-XL IGU
    • SuperLite® X-45/60/90
    • SuperLite® II-XL 45
    • Ceramics
    • Fire Resistive Glass Tested to ASTM E119 / UL 263 / ULC S101; Blocks smoke, flames and radiant heat.
    • SuperLite® II-XL 60
    • SuperLite® II-XL 90
    • SuperLite® II-XL 120
    • SuperLite® II-XLB 60
    • SuperLite® II-XLB 120
    • SuperLite® II-XLM 60
    • SuperLite® II-XLM 120
    • SuperSecure® II-XLS 45-120
    • Fire Rated Walls 60-120 minute fire resistive glass and frame assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® Architectural Series Fire Resistive
    • GPX® Curtain Wall
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Blast System
    • GPX® EZ Frame
    • Fire Rated Doors Full vision 20-45 minute fire protective doors and 60-90 minute temperature rise doors tested to NFPA 252 / UL 10C / ULC S104.
    • GPX® Architectural Series Fire Protective
    • GPX® Architectural Series Fire Resistive
    • GPX® Builders Series Fire Protective
    • GPX® Builders Series Temperature Rise
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Vision Kit
    • Fire Rated Openings 20-45 minute fire protective glass and framing assemblies tested to NFPA 257 / UL 9 / ULC S106.
    • GPX® Architectural Series Fire Protective
    • GPX® Builders Series Fire Protective
    • GPX® EZ Frame
    • Fire Rated Floors 60-120 minute fire resistive glass floor assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® FireFloor
    • Fire Rated Fences 20-60 minute fire rated glass fence for WUI areas or designated fire zones.
    • SAFTI FENCE
    • Specialty Glass
    • Laminated Safety Glass
  • Literature
  • Specs
  • Details
  • Videos
  • Resources
    About Us
    Videos
    Case Studies
    Articles
    Blogs
    Continuing Education
    Literature
    BIM Library
    Industry Links
    Press Releases
    Testimonials
    Technical Bulletins
    Newsletters
    Product Selector
  • Gallery
  • Contact
    Contact Us
    Meet Our Team
    Find Your Local Rep
    Request a Quote
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Videos
  • Resources
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Contact
    • Contact Us
    • Meet Our Team
    • Find Your Local Rep
    • Request a Quote
Menu
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Videos
  • Resources
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Contact
    • Contact Us
    • Meet Our Team
    • Find Your Local Rep
    • Request a Quote
Articles
Code Education
How Fire Rated Glass Meets Lot Line Requirements Without Sacrificing Design
Code Education

How Fire Rated Glass Meets Lot Line Requirements Without Sacrificing Design

BySAFTI FIRST Team
| September 24, 2020

Designers can use advanced fire rated glass technology in the building envelope near or on the lot line while improving the building’s aesthetic and performance.

Fire rated glass fulfills the designer’s goals of having unobstructed views and natural light. In cities like New York, Chicago, San Francisco or Boston where buildings are typically in close proximity to one another, designers can turn to fire rated glass to meet lot line requirements without sacrificing transparency. When employing this strategy, determining when fire rated requirements apply, the type of fire rated glass allowed (whether its fire protective or fire resistive), or how much fire rated glass can be used are just some of the factors that designers have to consider.

Explaining Lot Line Requirements

The fire resistance rating for exterior walls is based on construction type, occupancy and fire separation distance as defined in Section 6 of the IBC. These fire resistance requirements range from no required rating to 3 hours. Exterior walls generally have a rating based solely on interior occupancy use and structural requirements. However, exterior walls that are 10 feet or less from the property line are required to have a fire resistance rating based on the proximity to adjacent buildings and interior occupancy conditions. The 2009 IBC increased this distance from five to 10 feet.

An exterior wall may or may not be allowed to have openings depending on the fire separation distance. Chapter 2 of the IBC defines fire separation distance as the distance measured from the building face to one of the following:

  • • The closest interior lot line.
  • • To the centerline of a street, an alley or public way.
  • • To an imaginary line between two buildings on the lot.

The distance shall be measured at right angles from the face of the wall.

Once the fire separation distance has been established, Table 705.8 in the IBC lay out the percentage of protected and unprotected openings and size limits allowed in exterior walls. When allowed, the codes distinguish between openings that are “unprotected” (no fire rating) with or without sprinklers, and “protected” (such as fire protective glazing in openings tested to NFPA 257/UL 9):

  • • UP, NS = Unprotected openings in buildings not equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  • • UP, S = Unprotected openings in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  • • P = Openings protected with an opening protective assembly in accordance with Section 705.8.2.

Fire protective glass like 45 minute ceramics tested to NFPA 257/UL 9 are either limited in size or prohibited altogether depending on the fire separation distance. Generally speaking, as the fire separation distance increases, the allowable opening area and the percentage of allowable fire protective openings increases.

However, these limitations do not apply to fire resistive glass tested to the more stringent ASTM E-119/UL 263 standard, which requires limiting the temperature rise to less than 250º F above ambient on the non-fire side. Designers can use fire resistive glass in areas where exterior openings are not permitted or limited in size per IBC Table 705.8. By using fire resistive glass, designers don’t have to sacrifice expansive clear views and abundant natural light in order to meet code requirements.

Two types of fire rated glazing recognized in the IBC: Fire Protective Glass vs Fire Resistive Glass as explained in this quick, informative video.

In addition to meeting lot line requirements in the code, these advanced fire resistive glazing systems can perform like the rest of the materials building envelope and even match the aesthetic of adjacent non-rated glazing systems.

Dynamic Curtain Wall Testing

Static curtain wall testing performed in a chamber is one way to determine a product’s ability to prevent air and water from entering the building. However, the information from this test is limited. This why dynamic curtain wall testing designed to duplicate real world conditions is preferred by owners, architects and building envelope consultants.

Today’s advanced fire resistive curtain wall systems are tested to AAMA 501.1, ASTM E284 and ASTM E331. In addition to air and water testing, these systems are also tested to AAMA 501.4, ASTM E330, interstory vertical displacement, thermal cycling and condensation evaluation.

The 1-hour fire resistive curtain wall at The Kensington in Boston successfully passed dynamic curtain wall testing. Architect: The Architectural Team, Inc. Glazier: Cheviot Corporation. Products used: SuperLite II-XL 60 in GPX Curtain Wall. Read the case study here.

Thermal Performance

Occupant comfort is a key factor when selecting glazing products for the building envelope. While glass gives the benefit of natural daylight, controlling heat and glare are important considerations as well. Today’s advanced fire resistive glass products can easily incorporate low-e or any energy performance glazing. Designers can also find both fire protective and resistive glass and framing components in the NFRC CMAST database, enabling them to simulate the U-factor, Solar Heat Gain Coefficient (SHGC) and Visual Light Transmission (VLT) of exterior fire rated glazing assemblies.

The large, 2 hour fire resistive exterior glass walls used on the penthouse of The Warehouse in New York’s Chelsea neighborhood incorporates high-performance glazing to meet the stringent energy requirements. Architect: Morris Adjmi Architects. Glazier: Vision Walls. Products used: SuperLite II-XLB 120 in GPX Architectural Series Framing. Read the case study here.

Multi-tasking Protection Against Other Threats

Advanced fire resistive glazing systems can multi-task to provide additional protection against various environmental and man-made threats. Fire resistive glazing manufacturers have tested and listed systems that also meet:

  • • Florida Product Approval, Texas Department of Insurance and UL certifications for hurricane;
  • • Up to UL 752 Level 8 for ballistic;
  • • US Department of Defense (DOD) Minimum Antiterrorism Standards for blast;
  • • ASTM F-1915 Grade 1-4 for forced entry.
2-hour, fire resistive and blast rated curtain wall at an Army Hospital in the west coast spanned 45 feet and canted out a few degrees. Architect: RLF/US Army Corps of Engineers. Glazier: Sashco. Products used: Blast-rated SuperLite II-XL 120 in the GPX Blast System. Read the case study here.

With the architectural community pushing the limits of what fire rated glass can do, manufacturers will continue to respond with innovative products that fulfill their design and performance needs.

Share:
PrevNext ArticleWhich Version of the IBC are you on?
Previous ArticleExterior Glass Walls, Windows & Doors – Commercial & Residential Glass | ArticleNext
Back to Articles

Engineering. Design. Code.

Whether you’re looking for fire-rated walls, doors, openings, floors or a specialty service, we have the solution for you. With over 40 years of experience in testing, innovating, and providing technologically advanced fire-rated glass and framing products, we deliver unyielding performance and quality at a competitive price.

Let's Talk!

  • 888.653.3333
    (English)
  • 888.653.3333 ext. 652
    (Spanish)
  • info@safti.com
  • Representative Map
Contact
Phone
888.653.3333 - English
888.653.3333 ext. 652 - Spanish
Fax
888.653.4444
Email
info@safti.com
Address
Corporate
100 N Hill Dr, Ste12, Brisbane, CA 94005
Factory
220 S R Street, Merced, CA 95341

Sign up for our Newsletter!

Get notified of industry updates and new product alerts.

AFFILIATE COMPANIES
Division 5
1850 Grogan Ave, Merced, CA 95341
888.653.3333
Division 8
1891 Wardrobe Ave, Merced, CA 95341
866.848.2667
© 2025 SAFTI FIRST. All rights reserved.​
Disclaimer & Privacy Policy | Cookie Policy
Instagram Linkedin Facebook Youtube Vimeo
Suggested Pages
Case Studies
Request a Quote
SuperClear® 45-HS-LI
Continuing Education
Request a Quote
Continuing Education
Videos
SuperClear® 45-HS-LI
Case Studies
This website uses cookies to ensure you get the best experience on our website.

This website uses cookies to ensure you get the best experience on our website.


This website uses cookies to improve user experience. A cookie file is stored in your web browser and allows the website to recognize you and make your next visit easier and the website more useful to you. By using our website, you consent to all cookies in accordance with our Cookies Policy. Learn more.
Functional Always active
The technical storage or access is strictly necessary for the legitimate purpose of enabling the use of a specific service explicitly requested by the subscriber or user, or for the sole purpose of carrying out the transmission of a communication over an electronic communications network.
Preferences
The technical storage or access is necessary for the legitimate purpose of storing preferences that are not requested by the subscriber or user.
Statistics
The technical storage or access that is used exclusively for statistical purposes. The technical storage or access that is used exclusively for anonymous statistical purposes. Without a subpoena, voluntary compliance on the part of your Internet Service Provider, or additional records from a third party, information stored or retrieved for this purpose alone cannot usually be used to identify you.
Marketing
The technical storage or access is required to create user profiles to send advertising, or to track the user on a website or across several websites for similar marketing purposes.
Manage options Manage services Manage vendors Read more about these purposes
View preferences
{title} {title} {title}