What is Fire Protective Glass?
Fire protective glass is a type of fire rated glass capable of containing flames and smoke, preventing it from transferring to other areas. It meets NFPA 257 / UL 9 / CAN/ULC S106 for use in fire rated windows or openings and NFPA 252 / UL 10B/10C / CAN/ULC S104 for use in fire rated door assemblies. All of our fire protective glass options meet ANSI Z97.1 Class A and CPSC Cat. II impact safety requirements. Listed and labeled by UL and/or Intertek and proudly USA-made.
Fire protective glass is typically fire rated from up to 45 minutes and limited to 25% of the wall area. They can also be used in 60-180 minute temperature rise doors up to 100 square inches. Depending on the fire separation distance, they can also be used in 45 and 90 minute exterior fire rated windows or openings.
The codes limit the use of fire protective glass because it cannot block radiant heat. To exceed the size limitations or use glazing where fire protective glazing is not allowed, designers can specify fire resistive glass instead.
Fire Protective Glass Options
SuperLite® I
20 Minute Fire Protective Glazing
Clear, economical glazing for 20 minute fire rated doors.
Superlite® I-XL
20-45 Minute Fire Protective Glazing
Directional without Hose Stream
Clear, economical glazing with directional, heat reflective properties. May require AHJ approval for 45 minute applications as this product is fire tested without hose stream.
SuperLite® II-XL 45
45 Minute Fire Resistive Glazing
Clear, fire protective glass with fire resistive qualities for use in all 45 minute applications as well as 30 minute walls (W-30) required by code.
SuperLite® I-XL IGU
20-45 Minute Fire Protective Glazing
Bi-Directional Without Hose Stream
Clear, economical glazing with bi-directional, heat reflective properties. May require AHJ approval for 45 minute applications as this product is fire tested without hose stream.
SuperLite® II-XL 45
45 Minute Fire Resistive Glazing
Clear, fire protective glass with fire resistive qualities for use in all 45 minute applications as well as 30 minute walls (W-30) required by code.
SuperClear® 45-HS-LI
45 Minute Fire Protective Glazing
Patented, low-iron, clear, economical glazing for all 45 minute applications.
SuperClear® 45-HS
Fire Protective Specialty Glazing
Patented, clear glazing for all 45 minute applications.
SuperLite® I
20 Minute Fire Protective Glazing
Clear, economical glazing for 20 minute fire rated doors.
Helps Contain Fire & Smoke
Our clear, fire protective glazing products contains flames and smoke to one area to slow the spread of fire. This allows building occupants to gain valuable time to escape, as well as minimize the damage to property by containing the fire to its origin. Unlike wired glass, our products are capable of staying in the opening for its prescribed fire endurance period without the need for wires, which actually weaken the glass.
Meet CPSC Cat. II Impact Safety Requirements
Our fire protective glazing products meet the ANSI Z97.1 Class A and CPSC Cat. II impact safety standard (the maximum federal impact standard for safety glazing) without the use of films or laminates. Compared to filmed wired glass, filmed ceramic or laminated ceramic, our fire protective glass products are more likely to survive the impact, thus reducing replacement costs over time.
Many Custom Options Available
Our fire protective glass products can be customized to include custom options such as security, energy performance, decorative and more. Our SuperClear® 45-HS and SuperClear® 45-HS-LI are approved glazing components in the NFRC CMAST database.
Fire Protective Glass Applications
Our fire protective glass can be used in the following applications: 45 minute interior fire rated windows or openings up to 25% of the wall area; 20-45 minute fire rated doors; 45 minute fire rated sidelites and transoms; 45 and 90 minute exterior fire rated windows or openings depending on the fire separation distance; 60-180 minute fire rated door vision lites up to 100 square inches.
Featured Videos
Browse our collection of educational video resources to help you learn more about fire rated glass and framing.
SAFTI FENCE by SAFTI FIRST®
SAFTI FENCE by SAFTI FIRST® is the ideal clear solution for 1 hour fire rated fencing around homes or entire developments near wildland-urban areas and designated fire zones. Tested, certified and listed by UL and Intertek, this revolutionary product uses advanced fire rated glazing technology that reflects the heat back to the fire source - helping prevent the spread of fire.
What is the safest and most affordable fire protective product available in the market today?
Season 1 Episode 6: What is the safest and most affordable fire protective product available in the market today? Tim Nass, VP of Sales at SAFTI FIRST®, answers our industry's most frequently asked questions.
The Latest Innovations in Fire Rated Glazing Product Technology
SAFTI FIRST®'s VP of Sales Tim Nass shares the latest innovations in fire rated glazing product technology, and how these advancements have influenced the architectural and design community. He discusses the evolution of fire rated glazing and how the introduction of SuperClear® 45-HS-LI, the clearest, 45 minute fire rated glazing product that meets fire, safety, and hose stream requirements, will provide an affordable and superior solution to brittle, expensive ceramics.
NEW! Revolutionary, Clear, USA-Made SuperClear® 45-HS-LI (Patented)
SAFTI FIRST®’s new SuperClear® 45-HS and SuperClear® 45-HS-LI are approved for glazing in all 45 minute doors, sidelites, transoms and openings in large sizes. Meets strict fire, hose stream and safety requirements without wires, tints, films or laminates. Made in the USA for fast lead times—at costs significantly less than ceramics or safety wired—with better VLT, STC and OITC performance values. UL listed and labeled. Patented.
Traditional Wired Glass is Not Safe
Traditional wired glass is made with steel wire mesh that acts as a reinforcement. During a fire test, the grid holds the glass in place. Although believed to make the glass stronger, the sharp wires actually pose more harm than good and can cause serious injuries to people who come in contact with the installation. Before the development of wire-free, safety rated fire-rated glass, schools used traditional wired glass because of its capacity to contain fires while still allowing people to look through doors and windows.
AHJ Approval for SuperLite I-XL
SuperLite® I-XL is fully listed for 20 minutes and approved by the GSA and AHJs as an alternate material for 45/60 minute applications without hose stream in accordance with Section 104.11, Alternative Materials, Design and Methods of Construction and Equipment, of the IBC. Learn more about the benefits of SuperLite® I-XL.