Features

  • Patented directional specialty tempered glazing tested without hose stream that provides partial radiant heat protection not available with ceramics.
  • Accepted by the GSA and AHJs across the country as an economical and value added alternative to traditional unsafe wired glass and expensive ceramics.
  • Meets the highest human impact safety requirements.
  • Approved for 20 minute applications without limitations.
  • Received a General Approval from the City and County of Los Angeles (RR25655). For a list of AHJs across the US that have approved SuperLite I-XL , click here.
  • Regularly specified for use in urban-wildfire exterior applications and perfect for property line requirements.
  • Available in specialty architectural make-ups.
  • Lifetime warranty.
  • USA manufactured for fast delivery and competitive pricing.
  • GSA Contract Holder
Fire Rating Application Max CV Area Max CV W Max CV H Stops
20 Minutes Steel Doors 3,341in² 35-1/8” 95-1/8” 5/8"
20 Minutes Steel Sidelites, Windows and Transoms 5,760 in² 96" 96" 5/8"
45 Minutes Steel Doors 3,341in² 35-1/8” 95-1/8” 5/8"
45 Minutes Steel Sidelites, Windows and Transoms 5,760 in² 96" 96" 5/8"

Specifications

  • Thickness: 1/4” (6 mm)
  • Weight: 3.0 lbs./sq.ft.
  • Sound Transmission Rating: STC 28
  • Fire Rating: 20-45 minutes without hose stream.
  • Impact Safety Rating: CPSC 16 CFR 1201 Cat. I and II
  • Solar Heat Gain Coefficient: 0.70 SHGC

Listings and warranty

SuperLite I-XL is listed and labeled by Intertek/Warnock-Hersey Inc. and Underwriters Laboratories, nationally recognized testing laboratories approved by OSHA.

Intertek-Logo_with-c      UL-Logo

See Warranty

Standards

UL 9, UL 10B, UL 10C, NFPA 80, NFPA 252, NFPA 257, ASTM E152, ASTM E163, ASTM E2074, ASTM E2010-01, CPSC 16 CFR 1201 Cat. II U.S. Pat. No. 5,910,620 This product requires AHJ approval because it does not pass the hose stream portion of the fire test.