Skip to content
  • QUOTE
  • 888.653.3333
  • info@safti.com
  • Products
    • Fire Protective Glass Tested to NFPA 252/257, UL 9/10C, ULC S104/S106; Blocks smoke and flames.
    • SuperLite® I
    • SuperClear® 45-HS
    • SuperClear® 45-HS-LI
    • SuperLite® I-XL
    • SuperLite® I-XL IGU
    • SuperLite® X-45/60/90
    • SuperLite® II-XL 45
    • Ceramics
    • Fire Resistive Glass Tested to ASTM E119 / UL 263 / ULC S101; Blocks smoke, flames and radiant heat.
    • SuperLite® II-XL 60
    • SuperLite® II-XL 90
    • SuperLite® II-XL 120
    • SuperLite® II-XLB 60
    • SuperLite® II-XLB 120
    • SuperLite® II-XLM 60
    • SuperLite® II-XLM 120
    • SuperSecure® II-XLS 45-120
    • Fire Rated Walls 60-120 minute fire resistive glass and frame assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® Architectural Series Fire Resistive
    • GPX® Curtain Wall
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Blast System
    • GPX® EZ Frame
    • Fire Rated Doors Full vision 20-45 minute fire protective doors and 60-90 minute temperature rise doors tested to NFPA 252 / UL 10C / ULC S104.
    • GPX® Architectural Series Fire Protective
    • GPX® Architectural Series Fire Resistive
    • GPX® Builders Series Fire Protective
    • GPX® Builders Series Temperature Rise
    • GPX® Hurricane
    • GPX® Ballistic
    • GPX® Vision Kit
    • Fire Rated Openings 20-45 minute fire protective glass and framing assemblies tested to NFPA 257 / UL 9 / ULC S106.
    • GPX® Architectural Series Fire Protective
    • GPX® Builders Series Fire Protective
    • GPX® EZ Frame
    • Fire Rated Floors 60-120 minute fire resistive glass floor assemblies tested to ASTM E119 / UL 263 / ULC S101.
    • GPX® FireFloor
    • Fire Rated Fences 20-60 minute fire rated glass fence for WUI areas or designated fire zones.
    • SAFTI FENCE
    • Specialty Glass
    • Laminated Safety Glass
  • Literature
  • Specs
  • Details
  • Videos
  • Resources
    About Us
    Videos
    Case Studies
    Articles
    Blogs
    Continuing Education
    Literature
    BIM Library
    Industry Links
    Press Releases
    Testimonials
    Technical Bulletins
    Newsletters
    Product Selector
  • Gallery
  • Contact
    Contact Us
    Meet Our Team
    Find Your Local Rep
    Request a Quote
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Videos
  • Resources
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Contact
    • Contact Us
    • Meet Our Team
    • Find Your Local Rep
    • Request a Quote
Menu
  • Products
    • Fire Protective Glass
    • Fire Resistive Glass
    • Fire Rated Walls
    • Fire Rated Doors
    • Fire Rated Openings
    • Fire Rated Floors
    • Fire Rated Fences
  • Literature
  • Specs
  • Details
  • Videos
  • Resources
    • About Us
    • Product Selector
    • Articles
    • Blogs
    • BIM Library
    • Case Studies
    • Newsletters
    • Press Releases
    • Continuing Education
    • Literature
    • Technical Bulletins
    • Testimonials
    • Industry Links
    • Videos
  • Gallery
  • Contact
    • Contact Us
    • Meet Our Team
    • Find Your Local Rep
    • Request a Quote
Articles
FIRE RATED GLASS IN EDUCATION FACILITIES
Fire Rated Glazing in Schools FAQs
FIRE RATED GLASS IN EDUCATION FACILITIES

Fire Rated Glazing in Schools FAQs

BySAFTI FIRST Team
| April 9, 2015

FAQ: Fire Rated Glazing in Schools

Fire Rated Glazing in Schools FAQs provides answers to common questions on fire rated glass & framing applications based on current IBC & testing requirements.

Q. Why can’t I use one type of fire rated glass for all my applications, especially since the print ad says from 20 minutes to 3 hours?

Architects and designers should be wary about products that are marketed using the fire endurance rating (20 minutes to 3 hours) without any reference to its overall performance or limitations. Why? Because having a one-size-fits-all approach to fire rated glass not only leads to faulty specifications, but also significant expense when fire marshals and building officials order the glass to be changed because the wrong product is installed.

Fire Rated Glazing in Schools FAQs

The current IBC recognizes 2 categories of fire rated glass “fire protective and fire resistive”. These two types of fire rated glass are based on the testing criteria that the product has met, not just the duration rating. Fire protective glass products are tested to NFPA 252/257 and blocks smoke and flames. They are typically used in 20-45 minute applications and subject to size limitations dictated by code. Fire resistive glass products are tested to ASTM E-119/NFPA 251/UL263 and blocks smoke, flames and radiant heat. They are typically used in 60-120 minute applications and are only subject to tested size limitations.

Q. What are my product options for 1 hour exit corridors?

Generally speaking, exit corridors have a fire resistance rating of 1 hour. Table 716.5 in the 2012 IBC outlines the requirements for door, sidelite and transom assemblies:

Doors: 20 minute fire protective glass tested without hose stream. Products include specialty tempered, safety wired glass, filmed ceramics and laminated ceramics. All these options meet CPSC Cat. I and II impact safety.

Sidelites: 45 minute fire protective glass tested with hose stream. Products include 45-minute fire resistive intumescent tempered units, specialty tempered, safety wired glass, filmed ceramics and laminated ceramics. All these options meet CPSC Cat. I and II impact safety.

Transoms: 45 minute fire protective glass tested with hose stream. Products include 45-minute fire resistive intumescent tempered units, safety wired glass, traditional wired glass, plain ceramics, filmed ceramics and laminated ceramics. This application does not require meeting CPSC impact safety requirements.

Table 716.6 in the 2012 IBC outlines the requirements for openings in 1 hour exit corridors:

Openings not exceeding 25% of the wall area: 45 minute fire protective glass tested with hose stream. Products include 45-minute fire resistive intumescent tempered units, specialty tempered, safety wired glass, filmed ceramics and laminated ceramics. All these options meet CPSC Cat. I and II impact safety.

Openings exceeding 25% of the wall area: 60 minute fire resistive glass tested with hose stream. Products include 60 minute fire resistive intumescent tempered units. This product also meets CPSC Cat. I and II impact safety.

The GSA and AHJs have allowed the use of a fire protective heat-reflective specialty tempered product tested without hose stream in 45 minute sidelites, transoms and openings for the cost benefits and added safety that it provides. Click here for a technical bulletin with information on obtaining AHJ approval.

Q. What are my product options for 1 and 2 hour exit enclosures/stairwells?

The IBC requires interior exit stairways be enclosed to protect building occupants from smoke, flames and radiant heat as they are exiting the building. Exit enclosures/stairwells four stories or more must be 2 hour fire resistance rated; exit enclosures/stairwells less than four stories must be 1 hour fire resistance rated.

Table 716.5 in the 2012 IBC spells out the door assembly requirements for 1 and 2 hour exit enclosure/stairwells:

Doors: 60 or 90 minute fire protective glass limited to 100 square inches. Products include specialty fire protective, safety wired glass, filmed ceramics and laminated ceramics. To exceed 100 square inches in the door vision panel, either 60 minute fire resistive intumescent tempered units must be used in 1 hour stairwells, and 90 minute fire resistive intumescent tempered units must be used in 2 hour stairwells.

Sidelites and Transoms: 60 or 120 min. fire resistive glass rated equal to the wall. Products include 60 minute fire resistive intumescent tempered units for 1 hour stairwells, and 120 minute fire resistive intumescent tempered units for 2 hour stairwells. Note that fire protective glazing like wired glass or ceramics are not allowed in this application.

Q. For 1 and 2 hour exit enclosures/stairwells, can I use fire protective glass in large sizes if the building is fully sprinklered?

Under the 2012 IBC, door vision panels glazed with fire protective glazing, such as ceramics and wired glass, are limited to 100 sq. inches, whether the building is fully sprinklered or not. To exceed 100 sq. inches in the door vision panel, fire resistive glazing must be used.

Under the 2009 and 2006 IBC, larger fire protective glazing in door vision panels may be used in 1-hour exit enclosure and exit passageway doors only where the building – not just the door assembly – is fully sprinklered.

Under the 2012, 2009 and 2006 IBC, fire protective glazing is not allowed in the sidelites, transoms and openings surrounding the 60 minute door, whether the building is fully sprinklered or not. The glazing must be fire resistive and rated equal to the wall.

Q. What type of framing should I use?

The framing should match the performance of the glass since the code treats them as assemblies, not separate components. In other words, if fire protective glass is specified, fire protective framing tested to NFPA 252/257 can be used. Likewise, if fire resistive glass is specified, fire resistive framing tested to ASTM E-119 should be used.

If fire protective framing is used with fire resistive glass, the whole assembly rating is lowered to fire protective. This mismatched assembly will not meet the code requirements for applications that require ASTM E-119, which are typically wall and door assemblies rated 60-120 minutes.

Q. We find that most of the glass breakage occurs in doors and sidelites, and when it breaks, we have to replace it. How can we save money on glass replacement over time?

Glazing in doors, sidelites and hazardous locations (as outlined in Chapter 24 of the IBC) must be able to meet CPSC Cat. I or II impact safety. However, not all fire protective, safety rated products perform the same way.

Safety wired glass, filmed ceramics and laminated ceramics achieve their CPSC Cat. II impact safety rating by incorporating a safety film that holds the pieces of glass together when impacted. The glass will break, but there will be no through penetration.

Specialty tempered glass achieve their CPSC Cat. II impact safety rating through the material itself “tempered glass” without the need of adding safety films or laminates. In this video, the tempered glass not only passed the CPSC Cat. II requirement, but survived the impact without damage. This means less likelihood of breakage and replacement compared to safety wired glass, filmed ceramics and laminated ceramics.

Not only that, specialty tempered glass is the most affordable option considering upfront costs. It is typically a third of the cost of filmed ceramic and about 20% of the cost of laminated ceramic when used in the same 20-minute door application (primarily found in 1 hour corridors). For the 45 minute sidelites and transoms in the same 1 hour corridor, 45-minute fire resistive units cost less than filmed or laminated ceramics used in the same application, while providing better impact safety, clarity and protection from dangerous radiant heat.

Q. What about other security considerations, such as added protection against ballistic attack or forced entry?

After tragic events at Sandy Hook, there has been more emphasis on keeping students and staff safe in case of an attack. School districts nationwide have considered upgrading windows and doors to meet ballistic or forced entry.

In areas where fire rating requirements exist, there are products available today that can meet these additional security requirements. SAFTI FIRST has fire and ballistic rated systems that can meet up to level 8 ballistic and level 1 attack resistance, while also meeting ASTM E-119 up to 2 hours. SAFTI FIRST also offers fire resistive glass products that provide the highest level of protection required by the rigorous standards established by the California Department of Corrections.

Q. Are any of these fire rated glass and framing products made in the USA?

Yes. SAFTI FIRST manufactures the SuperLite glass products and SAFTIfire Framing products in their 50,000 square foot facility in Merced, CA. SAFTI FIRST is also the first and only single-source, USA-manufacturer of fire resistive glass and framing products. This means faster lead times and competitive pricing, with savings passed to our customers.

Click here to view our comprehensive line of fire rated glass products.

Click here to view our comprehensive line of fire rated framing products.

Have more questions on fire rated glass and framing? Send them to codesupport@safti.com and our technical representative will be happy to assist you.

Share:
PrevNext ArticleSafeguarding Schools from Radiant Heat
Previous ArticleABCs of School Fire ProtectionNext
Back to Articles

Engineering. Design. Code.

Whether you’re looking for fire-rated walls, doors, openings, floors or a specialty service, we have the solution for you. With over 40 years of experience in testing, innovating, and providing technologically advanced fire-rated glass and framing products, we deliver unyielding performance and quality at a competitive price.

Let's Talk!

  • 888.653.3333
    (English)
  • 888.653.3333 ext. 652
    (Spanish)
  • info@safti.com
  • Representative Map
Contact
Phone
888.653.3333 - English
888.653.3333 ext. 652 - Spanish
Fax
888.653.4444
Email
info@safti.com
Address
Corporate
100 N Hill Dr, Ste12, Brisbane, CA 94005
Factory
220 S R Street, Merced, CA 95341

Sign up for our Newsletter!

Get notified of industry updates and new product alerts.

AFFILIATE COMPANIES
Division 5
1850 Grogan Ave, Merced, CA 95341
888.653.3333
Division 8
1891 Wardrobe Ave, Merced, CA 95341
866.848.2667
© 2025 SAFTI FIRST. All rights reserved.​
Disclaimer & Privacy Policy | Cookie Policy
Instagram Linkedin Facebook Youtube Vimeo
Suggested Pages
Case Studies
Request a Quote
SuperClear® 45-HS-LI
Continuing Education
Request a Quote
Continuing Education
Videos
SuperClear® 45-HS-LI
Case Studies
This website uses cookies to ensure you get the best experience on our website.

This website uses cookies to ensure you get the best experience on our website.


This website uses cookies to improve user experience. A cookie file is stored in your web browser and allows the website to recognize you and make your next visit easier and the website more useful to you. By using our website, you consent to all cookies in accordance with our Cookies Policy. Learn more.
Functional Always active
The technical storage or access is strictly necessary for the legitimate purpose of enabling the use of a specific service explicitly requested by the subscriber or user, or for the sole purpose of carrying out the transmission of a communication over an electronic communications network.
Preferences
The technical storage or access is necessary for the legitimate purpose of storing preferences that are not requested by the subscriber or user.
Statistics
The technical storage or access that is used exclusively for statistical purposes. The technical storage or access that is used exclusively for anonymous statistical purposes. Without a subpoena, voluntary compliance on the part of your Internet Service Provider, or additional records from a third party, information stored or retrieved for this purpose alone cannot usually be used to identify you.
Marketing
The technical storage or access is required to create user profiles to send advertising, or to track the user on a website or across several websites for similar marketing purposes.
Manage options Manage services Manage vendors Read more about these purposes
View preferences
{title} {title} {title}